How to calculate voltage drop the easy way

Voltage drop shows up on exams and in real life on long runs. Here's the formula, a worked example, and what's considered acceptable.

94K views on YouTube · Go comment on YouTube →

The breakdown, in plain English

  • Single-phase formula: VD = (2 × K × I × L) ÷ CM.
  • K is the resistance constant: about 12.9 for copper, 21.2 for aluminum.
  • I is the load in amps, L is the one-way length in feet, CM is the wire's circular mil area (from Chapter 9, Table 8).
  • For three-phase, swap the 2 for 1.732.
  • The code recommends no more than 3% drop on a branch circuit and 5% total. That's a recommendation in the notes, not a hard rule, but exams ask about it.

Worked example

Example: 16 A at 120 V, 100 ft one way, #12 copper

  1. #12 copper = 6,530 circular mils.
  2. 2 × 12.9 × 16 × 100 = 41,280.
  3. 41,280 ÷ 6,530 = 6.32 volts dropped.
  4. 6.32 ÷ 120 = 5.3%. That's over 3%, so you'd upsize to #10.

Codes to look up

NEC 210.19(A) Informational Note

Sizing branch circuits for about 3% drop, and 5% total with the feeder, gives reasonable efficiency.

NEC Chapter 9, Table 8

Lists the circular mil area and resistance of each wire size.

These are plain-English summaries, not the code's exact wording. Always check the full section in the NEC edition your area has adopted, plus local amendments.