How to calculate a range in a dwelling load calculation (220.55)

Ranges are one of the trickiest parts of a whole-house load calculation. Lesson 3.2 walks through the demand table. Note: in the 2026 NEC, Article 220's dwelling load calcs moved to Article 120, so 220.55 is now 120.55.

112K views on YouTube · Go comment on YouTube →

The breakdown, in plain English

  • You don't add the nameplate rating of a range straight in. You use the demand table, which allows less than the nameplate because ranges rarely run everything at once.
  • One range rated 12 kW or less: use 8 kW (Column C).
  • Over 12 kW: add 5% to that 8 kW for every kW (or major fraction) above 12.
  • Smaller cooking appliances can use the lower columns of the table instead. Read the table notes carefully, because the exam loves them.

Worked example

Example: one 14 kW range

  1. 14 kW − 12 kW = 2 kW over.
  2. 2 × 5% = 10% increase.
  3. 8 kW × 1.10 = 8.8 kW demand load.

Codes to look up

NEC 220.55 (120.55 in 2026)

Household ranges and cooking appliances can use the demand factors in the table instead of their full nameplate rating.

NEC Table 220.55, Note 1

For a range over 12 kW, increase the Column C value by 5% per kW above 12.

These are plain-English summaries, not the code's exact wording. Always check the full section in the NEC edition your area has adopted, plus local amendments.