Free Videos · Exam Prep

Required 20-amp circuits and general lighting circuits in a house

Lesson 4.4 covers two things that show up on every residential exam: the 20-amp circuits a house is required to have, and how many general lighting circuits the square footage calls for.

100K views on YouTube · Go comment on YouTube →

The breakdown, in plain English

  • Kitchen and dining small-appliance receptacles: at least two 20-amp circuits.
  • Laundry: at least one 20-amp circuit.
  • Bathroom receptacles: at least one 20-amp circuit.
  • Garage (with power): at least one 20-amp circuit for the receptacles.
  • General lighting load for a dwelling is figured at 3 volt-amperes per square foot.

Worked example

Example: a 2,000 sq ft house

  1. 2,000 sq ft × 3 VA = 6,000 VA.
  2. 15-amp circuits: 120 V × 15 A = 1,800 VA each. 6,000 ÷ 1,800 = 3.33, round up to 4 circuits.
  3. 20-amp circuits: 120 V × 20 A = 2,400 VA each. 6,000 ÷ 2,400 = 2.5, round up to 3 circuits.

Codes to look up

NEC 210.11(C)

A dwelling needs 20-amp branch circuits for the small-appliance, laundry, bathroom and garage receptacles.

NEC 220.14(J) / Table 220.12

Dwelling general lighting load is figured at 3 VA per square foot (location depends on the code cycle).

These are plain-English summaries, not the code's exact wording. Always check the full section in the NEC edition your area has adopted, plus local amendments.

Find it faster on test day

Get a code book that's already tabbed and highlighted.

On an open-book exam, speed wins. Every book is tabbed and highlighted by hand so you can flip straight to sections like these.

Keep learning